This assessment shows how an engineer can find, rate and control the risks in a building heating, ventilation and cooling system. Eight risks were chosen because they are plausible in everyday design, commissioning and operation. Refrigerant release, legionella growth and electrical or combustion hazards carry the highest natural severity, while sizing mismatch and maintenance backlogs are more likely but cause steady harm. Each risk is scored before controls and again after existing and added controls. Most risks fall to Medium or Low once the proposed controls are in place, but electrical and combustion hazards stay at Medium because their impact remains serious. The first actions are isolation procedures, carbon monoxide sensing, a water treatment routine and a witnessed controls test. The building is a teaching example, so every score illustrates method, not a real plant.
Scope
This assessment covers the design, commissioning, operation and maintenance of a building heating, ventilation and air conditioning system, including gas boilers, air cooled chillers, air handling units, ductwork, controls and refrigerant circuits. It looks at risks to people, equipment, air quality, energy use and occupancy. It does not describe any real building, plant or jurisdiction. Location, applicable codes, plant size and contractor arrangements are assumptions made for teaching.
Context
The example building has a mechanical services engineer, a facilities manager, two maintenance technicians, an outsourced controls contractor and an external commissioning agent. Plant includes gas fired boilers, chillers with refrigerant circuits, air handling units with heat recovery, and a building management system that schedules and monitors all plant. Each risk is scored before controls to show its natural level, then again after the existing controls and the additional controls proposed. Specialist review by a licensed engineer is needed before any real design or work is carried out.
Objectives, assets and stakeholders
The objective is to keep occupants, staff and the public safe, provide reliable comfort conditions, control energy use and meet the legal duties that apply to plant. The assets in scope are the boilers, chillers, air handling units, ductwork, refrigerant circuits, water systems, electrical panels and the building management system. Stakeholders include maintenance staff, occupants, the building owner, the controls contractor, the commissioning agent, suppliers and the local authorities that enforce building and environmental rules. Clear roles matter: every risk has one owner role, and the facilities manager keeps the register current and reports to the owner each quarter.